User Tools

Site Tools


gas_handling_system

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
Next revision Both sides next revision
gas_handling_system [2016/08/15 18:33]
pereira
gas_handling_system [2017/01/22 16:56]
pereira [Tracking Gas bottles pressures]
Line 1: Line 1:
 ====== Detector gas handling system ====== ====== Detector gas handling system ======
  
 +  * [[#General information]]
 +  * [[#LabView Control Program]]
 +  * [[#Preparation of Gas bottles|Preparation of Gas bottles for filling of detectors]]
 +  * [[#Filling Ion Chamber with Gas]]
 +  * [[#Filling CRDC1 and CRDC2 with Gas]]
 +  * [[#Removing Gas from Focal Plane Detectors]]
 +  * [[#Tracking Gas bottles pressures|Tracking Gas bottles pressures from Barney]]
 +  * [[#Replacing gas bottles]]
 ===== General Information ===== ===== General Information =====
 Required controls and monitoring Required controls and monitoring
Line 6: Line 14:
   * PanelMate **S800vac.ui page 07**: Focal Plane Detector   * PanelMate **S800vac.ui page 07**: Focal Plane Detector
  
-The gas handling systems for both Focal Plane gas-filled detectors – the [[Detectors#Ionization Chamber|Ionization Chamber]] and the [[Detectors#Cathode Readout Drift Chambers (CRDC)|CRDCs]] – are remotely controlled via a single LabView application running on the computer [[Software|S800FP-PC]] in the S3 vault. This computer can be accessed remotely from the desktop of computer [[Software#u6pc5 (data U6)|u6pc5]], by clicking in the icon **S800 Vault PC**, or by typing ''rdesktop -d NSCL_USER -u s800 -g 1600x1000 35.9.56.104'' from a Linux terminal. Once the virtual session in S800FP-PC is open, the gas handling system can be opened by clicking in the corresponding icon on the desktop **FPGHS_TCPIP-II**. This icon opens the local directory 'C:/Users/s800/Desktop/FPGHS_TCPIP-II'. Once there, run the Labview executable **FPGHS_TCPIP-II.exe** +The gas handling systems for both Focal Plane gas-filled detectors – the [[Detectors#Ionization Chamber|Ionization Chamber]] and the [[Detectors#Cathode Readout Drift Chambers (CRDC)|CRDCs]] – are remotely controlled via a single LabView application running on the computer [[Software|S800FP-PC]] in the S3 vault. This computer can be accessed remotely from the desktop of computer [[Software#u6pc5 (data U6)|u6pc5]], by clicking in the icon **S800 Vault PC**, or by typing ''rdesktop -d NSCL_USER -u s800 -g 1600x1000 35.9.56.104'' from a Linux terminal. Once the virtual session in S800FP-PC is open, the gas handling system can be opened by clicking in the corresponding icon on the desktop **FPGHS_TCPIP-II**. This icon opens the local directory ''C:/Users/s800/Desktop/FPGHS_TCPIP-II''. Once there, run the Labview executable **FPGHS_TCPIP-II.exe** 
  
 Note that since the same roughing pump drives the gas handling systems for both gas-filled detectors, extra precautions must be taken to protect one detector from the pressure of the other detector. The fact that the same pump drives both systems is not indicated on the graphics for the LabView control application Note that since the same roughing pump drives the gas handling systems for both gas-filled detectors, extra precautions must be taken to protect one detector from the pressure of the other detector. The fact that the same pump drives both systems is not indicated on the graphics for the LabView control application
Line 150: Line 158:
   * Enter S3 vault and close main valves on [[#Preparation of gas bottles|gas bottles]]: P-10 for the [[Detectors#Ionization Chamber|ionization chamber]] (C<sub>4</sub>H<sub>10</sub>) and CF<sub>4</sub> (tetrafluoromethane) for the [[Detectors#Cathode Readout Drift Chambers (CRDC)|CRDCs]]    * Enter S3 vault and close main valves on [[#Preparation of gas bottles|gas bottles]]: P-10 for the [[Detectors#Ionization Chamber|ionization chamber]] (C<sub>4</sub>H<sub>10</sub>) and CF<sub>4</sub> (tetrafluoromethane) for the [[Detectors#Cathode Readout Drift Chambers (CRDC)|CRDCs]] 
  
-===== Tracking Gas bottles pressures ===== +===== Replacing gas bottles =====
-In order to track the status of the gas bottles for the [[Detectors#Ionization Chamber|ionization chamber]], the  [[Detectors#Cathode Readout Drift Chambers (CRDC)|CRDCs]], and the [[Detectors#[Tracking Parallel Plate Avalanche Counters (TPPAC)]|TPPAC]], it is possible to monitor their remaining pressures from Barney. Just open the **A1900** page, then **Tools**, and then **Gas Status**. The following window will be displayed:+
  
- 
- 
-{{:wiki:gas-bottles-status.jpg?900|Barney display of pressures of all "supported" gas detectors in the lab}} 
gas_handling_system.txt · Last modified: 2023/05/11 11:29 by pereira