User Tools

Site Tools


gas_handling_system

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
Next revision Both sides next revision
gas_handling_system [2017/01/31 12:03]
pereira [Filling Ion Chamber with Gas]
gas_handling_system [2017/06/07 13:15]
pereira
Line 50: Line 50:
            * The display unit for the pressure at the pump has a needle indicator and is mounted under the [[Stations#Focal Plane Station|focal plane]] on the south support post             * The display unit for the pressure at the pump has a needle indicator and is mounted under the [[Stations#Focal Plane Station|focal plane]] on the south support post 
       * Ensure that the main valves on the gas bottles are open (see pictures below)       * Ensure that the main valves on the gas bottles are open (see pictures below)
 +      * Open valves downstream of regulators in each bottle
       * Ensure that the gas bottles are not empty       * Ensure that the gas bottles are not empty
            * The gas regulators are not normally adjusted. They should all be set to provide a pressure around 20 psi            * The gas regulators are not normally adjusted. They should all be set to provide a pressure around 20 psi
Line 79: Line 80:
           * Click on the tab labeled **Slot 8 (M-card) IC** to access the page with the pressure set point control           * Click on the tab labeled **Slot 8 (M-card) IC** to access the page with the pressure set point control
           * Enter the desired pressure (typically 300 Torr) in the field under the knob labeled Set Point           * Enter the desired pressure (typically 300 Torr) in the field under the knob labeled Set Point
-          * Click button labeled **AUTO Mode** on left to start filling/regulation+          * Click button labeled **Update Set Point** 
 +          * Click button labeled **Return to AUTO Mode** on left to start filling/regulation
           * Click the **Valves** tab at the top of the LabView window to return to the overview display of the gas handling system to monitor filling. The flow readings for MFC #1 will increase and eventually disappear as the readout value overflows the display field (this is normal behavior)           * Click the **Valves** tab at the top of the LabView window to return to the overview display of the gas handling system to monitor filling. The flow readings for MFC #1 will increase and eventually disappear as the readout value overflows the display field (this is normal behavior)
-      * If necessary, the filling process can be stopped at any time by pressing the valve button labeled **Close MFC #1** 
       * Open **valve 9**       * Open **valve 9**
 +      * If necessary, the filling process can be stopped at any time by pressing the valve button labeled **Close MFC #1**
       * The filling process will take several minutes       * The filling process will take several minutes
  
Line 111: Line 113:
   * Fill CRDCs   * Fill CRDCs
       * Enter the desired fill pressure and start the automatic filling process       * Enter the desired fill pressure and start the automatic filling process
-          * Click the **Zero Sensor** button 
           * Click on the tab labeled **Virtual Ch. 0 (CRDC)** to access the page with the pressure set point control           * Click on the tab labeled **Virtual Ch. 0 (CRDC)** to access the page with the pressure set point control
           * Enter the desired pressure (typically 40 Torr) in the field under the knob labeled **Set Point**           * Enter the desired pressure (typically 40 Torr) in the field under the knob labeled **Set Point**
 +          * Click button labeled **Update Set Point**
           * Click button labeled **Return to AUTO Mode** on left to start filling/regulation           * Click button labeled **Return to AUTO Mode** on left to start filling/regulation
           * Click the **Valves** tab at the top of the LabView window to return to the overview display of the gas handling system to monitor filling. The flow readings for MFC #2 and MFC #3 will increase. The LabView application controls the gas mixing ratio based on the flow ratio (scaled with a calibration constant)           * Click the **Valves** tab at the top of the LabView window to return to the overview display of the gas handling system to monitor filling. The flow readings for MFC #2 and MFC #3 will increase. The LabView application controls the gas mixing ratio based on the flow ratio (scaled with a calibration constant)
-      * If necessary, the filling process can be stopped at any time by pressing the valve button labeled **Close MFCs #2 & #3** 
       * Open **valve 25**       * Open **valve 25**
 +      * If necessary, the filling process can be stopped at any time by pressing the valve button labeled **Close MFCs #2 & #3**
       * The filling process will take several minutes       * The filling process will take several minutes
  
Line 157: Line 159:
   * Open **valves 6 and 22**   * Open **valves 6 and 22**
  
-  * Enter S3 vault and close main valves on [[#Preparation of gas bottles|gas bottles]]: P-10 for the [[Detectors#Ionization Chamber|ionization chamber]] (C<sub>4</sub>H<sub>10</sub>) and CF<sub>4</sub> (tetrafluoromethane) for the [[Detectors#Cathode Readout Drift Chambers (CRDC)|CRDCs]] +  * Enter S3 vault and close valves downstream of regulators in [[#Preparation of gas bottles|gas bottles]]: P-10 for the [[Detectors#Ionization Chamber|ionization chamber]] (C<sub>4</sub>H<sub>10</sub>) and CF<sub>4</sub> (tetrafluoromethane) for the [[Detectors#Cathode Readout Drift Chambers (CRDC)|CRDCs]] 
  
 ===== Tracking Gas bottles pressures ===== ===== Tracking Gas bottles pressures =====
gas_handling_system.txt · Last modified: 2023/05/11 11:29 by pereira