Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
Next revision Both sides next revision
daq:daq [2015/10/02 13:56]
weisshaa [This is DAQ page for the 2015 campaign]
daq:daq [2019/11/27 14:09]
jing [miscellaneous]
Line 4: Line 4:
  
   * S800-Gretina control [[docsS800Grt|docsS800Grt]] ​   * S800-Gretina control [[docsS800Grt|docsS800Grt]] ​
-======= ​Misc 2015 ====== +  * {{ :​daq:​ulm-e16011_names.png?​linkonly |S800 Trigger GUI}} 
-  * Dual homed NSCL machines are ddasdaq2 ​and ddasdaq3 +======= ​Troubleshoot ​====== 
-  +  * S800-Gretina not correlated: Check CC setfile ~s800/​converged_daq/​Scripts/​CC0105Begin.tcl for extsynch ​and extclock
-====== DAQ Setup 2015 ======+
  
-  * Q5P4 Seg 31 values are negative. Appears to be problem with digitizer. +======= Decomp Information ====== 
-  * Q5P1 can not be in trigger. +  * [[easy_decomp_calibrations|Easy Gretina Decomp File Creation]] 
-  * Run 106 - Taken with north hemisphere. ​ All detectors biased to 3000 V.  Q1 Q2 Q6 Q8 all in trigger. Before full voltage benchmark run. +  * [[decomp_calibrations|Gretina Decomp Calibrations Explanation]]
-  * North Hemisphere Hole map :  +
-    +
-^  Quad  ^  Hole  ^  +
-^  Q1  | 24 | +
-^  Q2  |  29 | +
-^  Q6  | 9 | +
-^  Q8  |  28 |+
  
-  * Q1 -> Hole 24Q2 -> Hole 29, Q6 -> Hole 9, Q8 -> Hole 28 +======= Gretina Computing ======= 
-  * South Hemisphere Hole map   +Gretina computer farm is maintained by LBNL computer group and local NSCL IT department. Nonetheless I put documents herebut we do NOT do anything to the GRETINA computers!
-    +
-^  Quad  ^  Hole  ^  +
-^  Q3  |  17 | +
-^  Q5  |  25 | +
-^  Q7  |  19 |+
  
 +
 +  * May 2019, documentation provided from Jackie: [[https://​docs.google.com/​document/​d/​1Aq5NkuEKBc4_5fx-95d2RaSZM08VQwVleYWr42QTsFg/​edit?​invite=CNr_nogM&​ts=5cd488d9|Gretina System Documentation]]
 +  * Instruction to shut down switches for NSCL power shutdown 12/5/2015 {{:​daq:​gretinaswitchesshutdown.pdf|}}
 +
 +======= NSCL GRETINA LaBr Array =======
 +
 +    * [[fastscint_daq| FastScint DAQ Quick Start]]
 +    * [[fastscint_daq_long | FastScint DAQ Details]]
 +
 +======= Misc 2019 ======
 +  * Dual homed NSCL machines are spdaq32 and spdaq45
 +
 +====== miscellaneous ======
 +  * Validation/​Trigger window width is set by Dig116_CS_X55WidthP,​ Dig116_CS_X55WidthN. N/P stands for positive/​negative maximum difference relative to Trigger timestamp which will be read out.
 +  * Bringing up just the EPICs screen: in gretina home **./​startGRETINA_EPICSdisplay**
 +  * Set trigger multiplicity:​ **caput Trig0_CS_FSCThr n** (n=0,​1,​2,​3... for mult 1,2,3,4...)
 +  * See trigger pulse width: **CheckLED.sh**  ​
 +  * Change trigger pulse width: **SETLEDWIN <# of 20ns ticks>**
 +  * Check timestamps, report boards that are out-of-sync:​ **CheckTS**
 +  * Force timestamps to reset, DO NOT USE DURING RUN!!!: **SINGLEIMPSYNC**
 +  * Warning script: run on a2 as gretina in ~/scripts: **./​warningMessage4.sh **
 +  * Check decomp stats  ** recordDecomp.sh | head -n50 **
 +  * [[Flash digitizer firmware]]
 +  * Check digitizer firmware version: on a2 or a1 terminal, type: DIGSNIDFW
 +
 +====== Reboot a2 ======
 +  * If a2 is rebooted due to system failure, two scripts need to be brought up
 +    * from ~gretina: nohup scripts/​warningMessage4.sh &
 +    * from ~gretina/​scripts/​watcherdir:​ nohup watcher &
 + The first is the alarm script that talks to users. ​ The second is responsible for two things: writing record{Counters,​Decomp,​Settings} in the current run directory and cleaning up cluster process issues (usually restarting broken processes) soon after starting or stopping runs.    ​

QR Code