Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision Both sides next revision
fillsystem:alarmresponse [2013/05/08 16:41]
weisshaa
fillsystem:alarmresponse [2013/05/23 08:52]
weisshaa
Line 2: Line 2:
  
 You need to log on gln1, see [[LN computer]]. Go to directory ~/scripts and run ./​run-gln-ui.sh which gives the fill system interface. ​ You need to log on gln1, see [[LN computer]]. Go to directory ~/scripts and run ./​run-gln-ui.sh which gives the fill system interface. ​
-Type help for getting overview on commands. Get familiar with the commands mon, fill, clr, coff, con, abort, load, quit+Type help for getting overview on commands. Get familiar with the commands mon, clr, ton, fill, coff, con, abort, load, quit
  
 In some cases you need to edit the fill-system configuration file ~/​gln/​gln.fig for setting new temperature thresholds. In order In some cases you need to edit the fill-system configuration file ~/​gln/​gln.fig for setting new temperature thresholds. In order
Line 27: Line 27:
   * Run run-gln-ui.sh   * Run run-gln-ui.sh
   * Say '​clr'​ to clear alarm   * Say '​clr'​ to clear alarm
-  * You need to re-enable filling of this detector+  * You need to re-enable filling of this detector ​(ton #det)
   * If this happens regularly you may want to increase the T high threshold in gln.fig (F3 directive, end in gln.fig)   * If this happens regularly you may want to increase the T high threshold in gln.fig (F3 directive, end in gln.fig)
  
Line 34: Line 34:
   * IMPORTANT: detector T increased by few Kelvin only, see example plot below.   * IMPORTANT: detector T increased by few Kelvin only, see example plot below.
   * Run run-gln-ui.sh   * Run run-gln-ui.sh
-  * Say 'fill det#', confirm that you want to fill it.+  * Say 'fill det# now', confirm that you want to fill it.
   * Say 'coff det#', this stops T checking (and alarming and disabling) of this detector   * Say 'coff det#', this stops T checking (and alarming and disabling) of this detector
   * Watch the fill, check for reasonable fill time (not that LN out is triggering much too early)   * Watch the fill, check for reasonable fill time (not that LN out is triggering much too early)

QR Code
QR Code fillsystem:alarmresponse (generated for current page)